Analysis of ground fault current distribution along nonuniform multi-section lines
2008
In case of a substation supplied by a combined overhead-cable line, most of the ground fault current flows through the cable sheaths and discharges into the soil surrounding the point of discontinuity, where cables are connected to the overhead line. In the paper a new method is presented for computing the ground fault current distribution in case of feeding line consisting of two or more different sections, i.e. part overhead and part underground cable. Besides the calculation of the earth current at the fault location, the leakage current at the transit/transition stations as well as at the overhead line towers can be evaluated, in order to ensure proper safety conditions. Based on the tw…
A Simple Method for Evaluating Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line
2008
When a substation is fed by a combined overhead-cable transmission line, a significant part of the ground fault current flows through cable sheaths and is discharged into the soil at the transition station where cables are connected to the overhead line. Such a phenomenon, known as ldquofault application transfer,rdquo may result in high ground potentials at the transition station which may cause shocks and equipment damage. The scope of this paper is to present new analytic formulas which can be used for the direct calculation of the fault current transferred at the transition station and its ground potential rise as well as the substation earth current. The proposed formulas allow evaluat…
Ground Fault Current Distribution in Substations Supplied by Nonuniform Multi-Section Lines
2007
he paper presents a general method for computing the distribution of substation ground fault current. The feeding line can be entirely homogeneous along its whole length or consisting of two or more different sections, i.e. part overhead and part underground cable. Based on the two-port theory, the proposed method allows to take into account all the relevant conductively and inductively coupled parameters which take part to the distribution of the fault current and can be easily implemented in a computer program. Numerical examples demonstrate the high efficiency of the proposed method.